set cord
Command Syntax
Parameters
The set cord command uses the following parameters:
email
hyst
loadmax
name
nomvolts
outofbal
pf
snmpt
va
watts
Sub-Parameters
The set cord command uses the following sub-parameters:
alarmhi
alarmlo
warnhi
warnlo
min <=alarmlo <=warnlo <=warnhi <=alarmhi <=max
Usage Guidelines
Admin level only
Command Access
Sets cord configuration values.
set cord email [disabled | enabled] <name | id | ALL>
set cord loadmax <name | id | ALL> <value>
set cord name <name | id> <name string>
set cord nomvolts <name | id | ALL> <value>
set cord outofbal [alarmhi | warnhi] <name | id | ALL> <value>
set cord outofbal hyst <value>
set cord pf [alarmlo | warnlo] <name | id | ALL> <value>
set cord pf hyst <value>
set cord snmpt [disabled | enabled] <name | id | ALL>
set cord va [alarmhi | alarmlo | warnhi | warnlo] <name | id | ALL> <value>
set cord va hyst <value>
set cord watts [alarmhi | alarmlo | warnhi | warnlo] <name | id | ALL> <value>
set cord watts hyst <value>
Email notifications for cord events.
Hysteresis between event state and recovery.
Maximum current load for a cord. 1-max factory current in show cords
command.
Name for the cord. 0-32 characters.
Nominal voltage for the cord. 0-max factory voltage in show cords command.
Out-of-balance; the percent power difference between phases of a cord. min
0%, max 200%, hyst 0-10% (default 2%).
Power factor. min 0.00, max 1.00, hyst 0.0-0.20 (default 0.02).
SNMP trap notifications for cord events.
Power (with power factor included). min 0VA, max (power capacity) in cstat
command, hyst 0-1000VA (default 100VA).
Power (without power factor included). Min 0W, max (power capacity) in cstat
command, hyst 0-1000W (default 100W).
High alarm value.
Low alarm value.
High warning alarm.
Low warning alarm.