set line
Command Syntax
Parameters
Sub-Parameters
Command Access
Sets line configuration values.
set line email [disabled | enabled] <name | id | ALL>
set line load [alarmhi | alarmlo | warnhi | warnlo] <name | id | ALL> <value>
set line load hyst <value>
set line snmpt [disabled | enabled] <name | id | ALL>
The set line command uses the following parameters:
Email
Email notification for line events.
Hyst
Hysteresis between event state and recovery.
Load
Current load for a line. min = 0A, max (current limit) in show lines command,
hyst 0.0-10.0A (default 1.0A).
SNMPT
SNMP trap notifications for line events.
The set line command uses the following sub-parameters:
alarmhi
High alarm value.
alarmlo
Low alarm value.
warnhi
High warning alarm.
warnlo
Low warning alarm.
min <= alarmlo <= warnlo <= warnhi <= alarmhi <= max
Admin level only