Show Ports - LEGRAND Server Technology PRO1 User Manual

Sentry switched dc pdu
Table of Contents

Advertisement

show phases
Command Syntax
Command Access
Example

show ports

Command Syntax
Command Access
Example
Shows phase configuration values.
show phases
Admin level only
Switched PDU: show phases
ID
Phase Name
--
----------
AA1
AA:L1-L2
AA2
AA:L2-L3
AA3
AA:L3-L1
SNMP
Email
ID
Notif.
Notif.
--
------
------
AA1
enabled
enabled
AA2
enabled
enabled
AA3
enabled
enabled
Voltage
Voltage
ID
Lo-Alrm
Lo-Warn
--
-------
-------
AA1
187.2V
197.6V
AA2
187.2V
197.6V
AA3
187.2V
197.6V
Common Phase Settings
Phase Voltage Hysteresis:
Phase Power Factor Hysteresis:
Shows port configuration values.
show ports
Admin level only
Switched PDU: show ports
ID
Port Name
--
---------
COM1
Console
COM2
Aux
PRO1 Sentry Switched DC PDU
Nominal
Voltage
-------
208V
208V
208V
Voltage
Voltage
PF
Hi-Warn
Hi-Alrm
Lo-Alrm
-------
-------
-------
218.4V
228.8V
--
218.4V
228.8V
--
218.4V
228.8V
--
2.0V
0.02
Locked
Baud
Timeout
------
----
-------
No
9600
5 min
No
115200
5 min
192 of 211
PF
Lo-Warn
-------
--
--
--
DSR Chk
RFTAG
-------
-----
enabled
enabled
enabled
disabled

Hide quick links:

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the Server Technology PRO1 and is the answer not in the manual?

Table of Contents