LEGRAND Server Technology PRO1 User Manual page 181

Sentry switched dc pdu
Table of Contents

Advertisement

set ups
Command Syntax
Parameters
Sub-Parameters
Command Access
Sets UPS device configuration values.
set ups addline <UPS#> <line name | id | ALL>
set ups commstr <UPS#> <get community string>
set ups delline <UPS#> <line name | id | ALL>
set ups host <UPS#> <hostname>
set ups oidspoll <UPS#> <oid>
set ups onbattery <UPS#> <value>
set ups onutility <UPS#> <value>
set ups port <UPS#> <port>
set ups type <UPS#> <value>
The set ups command uses the following parameters:
UPS#
The number of the UPS to change. 1-8.
addline
Adds the specified line to be protected by the UPS.
commstr
Sets the community string for polling the UPS by SNMP. 0-32 characters.
delline
Removes the specified line from a UPS.
host
Hostname for polling the UPS by SNMP. 0-63 characters.
oidspoll
The OID for getting the "on battery"/"on utility" value when polling the UPS
by SNMP.
onbattery
Value of the OID when the UPS is in an "on battery" state. 1-65535.
onutility
Value of the OID when the UPS is in an "on utility" state. 1-65535.
port
Port number for polling the UPS by SNMP. 1-65535 (default 161).
type
Sets the type of the UPS; sets default commstr, oidspoll, onbattery, onutility,
and port. 1-11.
The set ups command uses the following sub-parameter:
oid
The OID string with sequences of a dot and a number. 1-65535.
Admin level only
PRO1 Sentry Switched DC PDU
181 of 211