set phase

Command Syntax
Parameters
Sub-Parameters
Command Access
set port
Command Syntax
Sets phase configuration values.
set phase email [disabled | enabled] <name | id | ALL>
set phase pf [alarmlo | warnlo] <name | id | ALL> <value>
set phase snmpt [disabled | enabled] <name | id | ALL>
set phase volts [alarmhi | alarmlo | warnhi | warnlo] <name | id | ALL> <value>
set phase volts hyst <value>
The set phase command uses the following parameters:
email
Sets email notifications for phase events.
hyst
Sets hysteresis between event state and recovery.
pf
Sets power factor. min 0.00, max 1.00, hyst 0.0-0.20 (default 0.02).
snmpt
Sets SNMP trap notifications for phase events.
volts
Sets voltage. min and max vary by product
min-max range, issue set cord nomvolts all command (press ESC to quit command).
The set phase command uses the following sub-parameters:
alarmhi
Sets high alarm value.
alarmlo
Sets low alarm value.
warnhi
Sets high warning value.
warnlo
Sets low warning value.
Admin level only
Sets serial port configuration values.
set port [baud | speed] [1200 | 2400 | 4800 | 9600 | 19200 | 38400 | 57600 | 115200]
<name | id >
set port dsrcheck [disabled | enabled] <name | id >
set port timeout <name | id > <timeout>
PRO1 Sentry Switched DC PDU
*
174 of 211
,
hyst 0.0-20 (default 0.02). * For the