LEGRAND Server Technology PRO1 User Manual page 176

Sentry switched dc pdu
Table of Contents

Advertisement

Parameters
The set sensor command uses the following parameters:
adc
Sets the analog-to-digital converter sensor. min 0, max 255, hyst 0-20 (default 1).
contact
Sets the contact closure sensor.
fan
Sets the fan values when a fan is present.
humid
Sets the humidity sensor. min 0%RH, max 100%RH, hyst 0-20%RH (default 2%RH).
temp
Sets temperature sensor. For Celsius: min -40°, max 123°, hyst 0-30°, default 1°; For
Fahrenheit: min -40°, max 253°, hyst 0-54°, default 2°.
water
Sets the water sensor.
email
Sets the email notifications for sensor events.
hyst
Sets the hysteresis between event state and recovery.
name
Sets the name of the sensor.
snmpt
SNMP trap notifications for sensor events.
scale
Sets temperature scale.
PRO1 Sentry Switched DC PDU