NEBS Statements
NEBS GR-1089-Core Information: Models 48DCWC and 48DCXC
These products are intended to be installed in Network Communications Facilities and in locations where
the NEC applies.
These products are suitable for installation in a Common Bonding Network (CBN).
These products may be installed in either a (DC-C) or (DC-I) configuration.
In the DC-C configuration, the ampacity of the conductor connecting the equipment frame to the BR
conductor shall be equal to, or greater than, the ampacity of the associated BR conductor.
"WARNING: The intra-building port(s) of the equipment or subassembly is suitable for connection to intra-
building or unexposed wiring or cabling only. The intra-building port(s) of the equipment or subassembly
MUST NOT be metallically connected to interfaces that connect to the OSP or its wiring.
These interfaces are designed for use as intra-building interfaces only (Type 2 or Type 4 ports as described in
GR-1089-CORE, Issue 5), and require isolation from the exposed OSP cabling. The addition of Primary
Protectors is not sufficient protection in order to connect these interfaces metallically to OSP wiring."