set unit
Command Syntax
Parameters
Sub-Parameters
Command Access
Sets PRO1 configuration values.
set unit assettag <name | id> <asset tag>
set unit display [auto | inverted | normal] <name | id | ALL>
set unit email [disabled | enabled] <name |id | ALL>
set unit identify [disabled | enabled] <name | id | ALL>
set unit name <name | id> <new name>
Confirmation required:
set unit purge <name | id | ALL>
set unit snmpt [disabled | enabled] <name | id | ALL>
The set unit command uses the following parameters:
assettag
The asset tag value of the unit. 0-32 characters.
display
Sets the orientation of the displays on a unit.
email
Email notifications for an event.
identify
Set to enable/disable flashing display.
name
The name of the unit. 0-32 characters.
odisporder
Sets the Web GUI and CLI outlet display order for a unit.
Note: The unit must have sequential switched outlets or this parameter will
be ignored.
osequence
Sets the outlet sequence order for a unit.
purge
Removes all stored information for a unit.
snmpt
SNMP trap notifications for unit events.
The set unit command uses the following sub-parameters:
auto
Set automatic display orientation using internal orientation sensor.
Inverted
Set display to be upside down.
normal
Set display to be right-side up; set outlet sequencing to be 1 to n.
reversed
Set outlet sequencing to be n to 1.
Admin level only
PRO1 Sentry Switched DC PDU
180 of 211