Restart Options for the Sentry DC PDU:
Note: About Unit Persistence:
The PRO1 products support unit persistence. This means that if a link unit is connected to a master unit, and the
link unit is disconnected (powered down or accidentally disconnected), and the master unit is restarted, the link
unit will be reported as "Not Found" after the restart because the link unit is no longer physically connected to the
master.
However, the association between the master/link units is retained to allow the continuation of alerts. If the
disconnected link unit is physically re-connected to the master, the "Not Found" status will return to "Normal"
status.
To intentionally remove a link unit from connection with a master unit, the link unit must be purged using the
Purge function.
Unit persistence affects all connected master/link units whether or not they are connected in a multi-linking
configuration.
This restart option ...
Restart
Restart and reset to factory
defaults
Restart and reset to factory
defaults, except network
Restart and download
firmware via FTP
Restart and generate a new
X.509 certificate
Restart and compute new
SSH keys
performs this action on the PRO1 ...
Performs a warm boot; system user/outlet/outlet group configuration settings and outlet
states are not changed or reset with the restart command.
Resets the non-volatile RAM where configuration values are stored. This option clears all
administrator-editabled fields and resets all CLI configurable options to their factory
default values, including all user accounts.
Resetting the PDU to factory default values also resets all TCP/IP and Telnet/Web
configurations. Reconfiguring TCIP/IP and Telnet/Web settings is required.
Same action as "Restart and reset to factory defaults" described directly above, but
network protocol settings are not changed.
New versions of firmware can be uploaded using FTP. To begin an FTP upload session,
you must first configure the FTP host address, username/password, filename, and file
path.
When initiating an FTP upload session, the PDU restarts and uploads the firmware file
specified with the FTP filename command from the previously configured FTP host.
Generates a new X.509 certificate issued and signed by a certificate-authority.
Generates new private and public SSH keys with the proper location and permisssion.
PRO1 Sentry Switched DC PDU
133 of 211