Commissioning

5.6 Restoring the factory settings

5.6
Restoring the factory settings
When must you restore the factory settings?
Restore the converter to the factory settings in the following cases:
• You do not know the converter settings.
• The line voltage was interrupted during commissioning and you were not able to
complete commissioning.
Restoring the factory settings when the safety functions are enabled
If you are using the integrated safety functions of the converter, e.g. "Safe Torque Off", you
must reset the safety functions separately from the remaining converter settings.
The settings of the safety functions are protected by a password.
Settings that are not changed when restoring the factory setting
The communication settings and the settings of the motor standard (IEC/NEMA) are kept
when restoring the factory setting.
5.6.1

Restoring the factory settings/delivery condition (without safety functions)

Procedure with Startdrive
1. Go online with the converter.
2. Select the command as follows from the project tree:
98
Operating Instructions, 09/2020, FW V4.7 SP13, A5E48681219B
SINAMICS G115D distributed drive