2.2 Technical Data

Mechanic
Material
Dimensions W x H* x L
* from upper edge of DIN 35 rail
- Coupler/Controller (Standard)
- Coupler/Controller (ECO)
- Coupler/Controller (FireWire)
- I/O module, single
- I/O module, double
- I/O module, fourfold
Installation
modular by
Mounting position
Marking
Connection
Connection type
Wire range
Stripped length
Contacts
Power jumpers contacts
Current via power contacts
Voltage drop at I
Data contacts
Climatic environmental conditions
Operating temperature
Storage temperature
Relative humidity
Resistance to harmful substances
Maximum pollutant concentration at
relative humidity < 75%
Special conditions
WAGO-I/O-SYSTEM 750
CANopen
Polycarbonate, Polyamide 6.6
- 51 mm x 65 mm x 100 mm
- 50 mm x 65 mm x 100 mm
- 62 mm x 65 mm x 100 mm
- 12 mm x 64 mm x 100 mm
- 24 mm x 64 mm x 100 mm
- 48 mm x 64 mm x 100 mm
on DIN 35 with interlock
double featherkey-dovetail
any position
marking label type 247 and 248
paper marking label 8 x 47 mm
CAGE CLAMP®
0.08 mm² ... 2.5 mm², AWG 28-14
8 – 9 mm,
9 – 10 mm for components with pluggable wiring
(753-xxx)
blade/spring contact
self-cleaning
10 A
max
< 1 V/64 modules
max
slide contact, hard gold plated
1.5 µm, self-cleaning
0 °C ... 55 °C,
-20 °C ... +60 °C for components with extended
temperature range (750-xxx/025-xxx)
-20 °C ... +85 °C
5 % to 95 % without condensation
acc. to IEC 60068-2-42 and IEC 60068-2-43
SO
S ≤ 10 ppm
H
2
Ensure that additional measures for components are
taken, which are used in an environment involving:
– dust, caustic vapors or gasses
– ionization radiation.
The WAGO-I/O-SYSTEM 750
Technical Data
≤ 25 ppm
2
• 13

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

750-337750-338

Table of Contents