WAGO -I/O-SYSTEM 750 Technical Description page 103

Modular i/o system canopen
Hide thumbs Also See for WAGO-I/O-SYSTEM 750:
Table of Contents

Advertisement

2. RxPDO:
contains max. the 1st to 4th 16 bit analog output. If no 16 bit analog outputs
exist, the sub index 0 has the default value 0, and this PDO is not used with its
default value.
Idx
0x1601
3. RxPDO:
contains maximum the 5
outputs exist, the sub index 0 has the default value 0, and this PDO is not used
with its default value.
Idx
0x1602
4. RxPDO:
contains maximum the 9th to 12
bit analog outputs exist, the sub index 0 has the default value 0, and this PDO
is not used with its default value.
Idx
0x1603
WAGO-I/O-SYSTEM 750
CANopen
S-Idx
Description
0
Number of mapped objects
1
1. mapped 16 bit analog output
2
2. mapped 16 bit analog output
3
3. mapped 16 bit analog output
4
4. mapped 16 bit analog output
th
th
to 8
S-Idx
Description
0
Number of mapped objects
1
5. mapped 16 bit analog output
2
6. mapped 16 bit analog output
3
7. mapped 16 bit analog output
4
8. mapped 16 bit analog output
S-Idx
Description
0
Number of mapped objects
1
9. mapped 16 bit analog output
2
10. mapped 16 bit analog output
3
11. mapped 16 bit analog output
4
12. mapped 16 bit analog output
Network Communication
bit analog output. If more than 4 16 bit analog
th
16 bit analog output. If not more than 8 16
CANopen
• 103
Default Value
None, possible values:
0: no analog output
1..4: 1..4 analog outputs
0x6411 01 10
0x6411 02 10
0x6411 03 10
0x6411 04 10
Default Value
None, possible values:
0: no analog output
1..4: 1..4 analog outputs
0x6411 05 10
0x6411 06 10
0x6411 07 10
0x6411 08 10
Default Value
None, possible values:
: no analog output
1..4: 1..4 analog outputs
0x6411 09 10
0x6411 0A 10
0x6411 0B 10
0x6411 0C 10