172 •
I/O Modules
Process Data Architecture for CANopen
750-637
The above Incremental Encor Interface Module has a total of 6 bytes of user
data in both the Input and Output Process Image (4 bytes of encor data and 2
bytes of control/status). The following table illustrates the Input and Output
Process Image, which have 6 bytes mapped into each image.
These modules present themselves with 2x3 bytes, so that the object 0x2600
for 3 byte Special Modules, Inputs and the object 0x2700 for 3 byte Special
Modules, Outputs are used. Therefore for each module one Subindex is occu-
pied
750-635, 753-635
The above Digital Pulse Interface module has a total of 4 bytes of user data in
both the Input and Output Process Image (3 bytes of module data and 1 byte of
control/status). The following table illustrates the Input and Output Process
Image, which have 4 bytes mapped into each image.
These modules present themselves with 1x4 bytes, so that the object 0x2800
for 4 byte Special Modules, Inputs and the object 0x2900 for 4 byte Special
Modules, Outputs are used. Therefore for each module one Subindex is occu-
pied.
Sub-
Offset
byte Destination
index
0
n
1
2
3
n+1
4
5
Sub-
Offset
byte Destination
index
0
1
n
2
3
Input and Output Process Image
C0/S0
D0
D1
C1/S1
D2
D3
Input and Output Process Image
C0/S0
D0
D1
D2
Remark
Control/Status byte 1
Data Value
Control/Status byte 2
Data Value
Remark
Control/Status byte
Data Value