Range of
application
Industrial areas
Residential areas
*)
Maximum power dissipation of the components
Bus modules
Fieldbus coupler/controller
Warning
The power dissipation of all installed components must not exceed the maxi-
mum conductible power of the housing (cabinet).
When dimensioning the housing, care is to be taken that even under high ex-
ternal temperatures, the temperature inside the housing does not exceed the
permissible ambient temperature of 55 °C.
WAGO-I/O-SYSTEM 750
CANopen
Required specification
emission of interference
EN 61000-6-4 (2001)
EN 61000-6-3 (2001)*)
The system meets the requirements on emission of interference in residential areas with
the fieldbus coupler/controller for:
ETHERNET
750-342/-841/-842/-860
LonWorks
750-319/-819
CANopen
750-337/-837
DeviceNet
750-306/-806
MODBUS
750-312/-314/ -315/ -316
750-812/-814/ -815/ -816
With a special permit, the system can also be implemented with other fieldbus cou-
plers/controllers in residential areas (housing, commercial and business areas, small-scale
enterprises). The special permit can be obtained from an authority or inspection office. In
Germany, the Federal Office for Post and Telecommunications and its branch offices
issues the permit.
It is possible to use other field bus couplers/controllers under certain boundary condi-
tions. Please contact WAGO Kontakttechnik GmbH & Co. KG.
The WAGO-I/O-SYSTEM 750
Required specification
immunity to interference
EN 61000-6-2 (2001)
EN 61000-6-1 (2001)
0.8 W / bus terminal (total power dissipation, sys-
tem/field)
2.0 W / coupler/controller