3. TxPDO:
contains maximum the 5
analog inputs exist, the sub index 0 has the default value 0, and this PDO is
not used with its default value.
Idx
0x1A02
4. TxPDO:
contains maximum the 9
analog inputs exist, the sub index 0 has the default value 0, and this PDO is
not used with its default value.
Idx
0x1A03
Initialization Manufacturer Specific Profile Area
This area is initialized as described in the object directory.
Initialization Standardized Device Profile Area
All supported objects are initialized, as defined in the DS 401 standard.
WAGO-I/O-SYSTEM 750
CANopen
th
th
to 8
S-Idx
Description
0
Number of mapped objects
1
5. mapped 16 bit analog input
2
6. mapped 16 bit analog input
3
7. mapped 16 bit analog input
4
8. mapped 16 bit analog input
th
th
to 12
S-Idx
Description
0
Number of mapped objects
1
9. mapped 16 bit analog input
2
10. mapped 16 bit analog input
3
11. mapped 16 bit analog input
4
12. mapped 16 bit analog input
Network Communication
16 bit analog input. If not more than 4 16 bit
16 bit analog input. If not more than 8 16 bit
CANopen
• 105
Default Value
None, possible values:
0: no analog input
1..4: 1..4 analog inputs
0x6401 05 10
0x6401 06 10
0x6401 07 10
0x6401 08 10
Default Value
None, possible values:
0: no analog input
1..4: 1..4 analog inputs
0x6401 09 10
0x6401 0A 10
0x6401 0B 10
0x6401 0C 10