Wiring
6.6.5
Energy store PMCenergy SD
PMCenergy SD
The energy stores are connected to the direct current intermediate circuit and they store the
energy that the motor produces in the generating operation. This energy is usually imple-
mented via brake resistors in power dissipation.
If the energy is required, for example, with the next acceleration cycle, the energy stores
supply the saved energy back in the intermediate circuit.
Operating Manual PMCtendo DD5
1002236-EN-04
NOTICE
High transient currents between connected intermediate circuits can destroy
the servo amplifier.
- Supply the servo amplifier from the same mains (identical mains voltage).
- Do not wire servo amplifiers with smaller outputs between two servo ampli-
fiers with higher outputs.
- Ensure that the total rated currents of all the servo amplifiers connected in
parallel in an intermediate circuit is not exceeded.
– 230 V series: Max. 24 A
– 480 V series: Max. 40 A
Energy store
Dimensions (HxWxD): 300 x 100 x 201 mm
96