Wiring
}
The EMC product standard EN 61800-3, which contains limit values and test methods
for noise emission and immunity for adjustable speed electrical power drive systems
(PDS):
–
–
Measures for ensuring the wiring is EMC-compliant are:
}
Earthing
}
Shielding
}
Filter
}
Chokes
6.5.1
Earthing
Earthing measures are a prerequisite for the effective use of additional EMC measures
such as shielding or filters:
}
All earthing points should be fed directly to the central earth bar (equipotential bonding
bar).
}
The connections must be low impedance and must be good conductors.
}
Connections should be kept as short as possible.
}
Connections to the earth bar should always be in star form.
}
Connections should be protected from corrosion.
}
Flexible earthing straps should be used on moving earth parts (e.g. machine parts,
gates). Ensure these earthing straps are as short and wide as possible.
}
Unused wires in a cable should be earthed at both ends.
6.5.2
Shielding
Shielding measures reduce noise energy (immunity of adjacent systems and devices to ex-
ternal influences):
}
Correct shielding of the following cables avoids interference coupling with
–
–
–
–
–
Operating Manual PMCtendo DD5
1002236-EN-04
Noise immunity: "Second environment" category (industrial environment)
Noise emission:
Category C2 (length of motor cable ≤ 10 m)
Category C3 (length of motor cable ≥ 10 m)
WARNING!
In a residential environment this product may cause high-frequency noise,
so that suppression measures may be required.
Motor cables
Cables to the external brake resistor
Encoder cables
Cables with digital and analogue signals
Cables to communications interfaces
86