10. Functional checks
10.2

Checking the ward functions

10.2.1
Call forwarding
When a call is not answered within a programmed time frame, it will be forwarded to
all rooms with activated presence states. Forwarded calls are presented on the dis-
play of the ComTerminal Flamenco and of the RoomTerminal Flamenco, and a tone
also signals such calls.
The ControlTerminal Flamenco and the ControlTerminal with doorplate Flamenco do
not emit a call tone. In rooms with these terminals, the staff presence combination
with call tone (77 0219 00...) is used to output the call tone. If a staff presence switch
(77 0212 00...) is installed in the room instead of the staff presence combination with
call tone, the staff presence switch must be configured so that it emits the call tone.
How to configure the call tone is described in the product leaflet for the presence
switch.
Rooms with ComTerminal Flamenco
Refer to the operating instructions for the ComTerminal Flamenco for details on the
handling of forwarded calls.
Check for each room:
 Is the call forwarding tone audible at the ComTerminal?
 Does the display of the ComTerminals show the correct room number?
 Can the call be answered? Can a speech connection be established to the calling
location?
 Can calls of call type "Call" be cancelled from the remote position?
Rooms with RoomTerminal Flamenco
Refer to the operating instructions for the RoomTerminal Flamenco for details on the
handling of forwarded calls.
Check for each room:
 Is the call forwarding tone audible at the RoomTerminal?
 Does the display of the RoomTerminal show the correct room number?
 Can the call be acknowledged?
Rooms with ControlTerminal Flamenco, ControlTerminal with door-
plate Flamenco
Check for each room: Is the call forwarding tone audible at the staff presence switch
(77 0212 00...) or at the staff presence combination with call tone (77 0219 00...)?
10.2.2
Corridor display
Check whether calls in the ward are correctly indicated at the corridor display.
10.2.3
Direction lamps
Check each direction lamp for the correct indication of the direction for the allocated
rooms.