Power supply unit UPS 60, Order No. 77 3400 10
7. Storage
If the power supply unit UPS 60 will not be used for an extended period of time, the connected
batteries must first be fully recharged to preclude battery damage due to total discharging. (Refer to
item 6 Battery service life).
For the charging process, the power supply unit UPS 60 shall be connected to the mains supply
for at least 4 hours, and the UPS function shall be activated by placing the bridging contact
between "x" and "y".
While the power supply unit UPS 60 is not used, the power supply unit UPS 60 must be
disconnected from the batteries of battery set for UPS 60 to prevent total discharge.
8. Spare parts
Spare part
Mains fuse, front plate (5 x 20) T 5.0 A
Output fuse, bottom 15 A FKS
Clamp for mains connection, 3-pole
Clamp for 24 V connection, 4-pole
Clamp for control and indicator outputs, 7-pole
Clamp for battery connection, 2 pole
Bridging contact EB 2 – 5 for control clamps "x" and "y"
9. Technical data
Input
Nominal input voltage
Input voltage range
Input frequency
Input current
Start-up current surge
Power factor
Output
Nominal current
Output voltage in mains mode
Output voltage in battery mode
Calculated output power
Rippling of nominal output current
Battery capacity to be connected
Charge current
Bridging time at nominal current
Battery voltage thresholds
Switching threshold for UPS mode
Switching threshold for warning before battery shut-
down
Switching threshold for total discharge protection
EMC CE-certified
Safety
Output
Test voltage PRI – SEC
Protection class
Ingress Protection
General
Permissible ambient temperature in operation
Permissible ambient temperature during storage and
transport
MTBF
English - 6
22 A at 115 V AC / 44 A at 230 V AC, typical
0.95 at 230 V AC / 0.98 at 115 V AC for full load
EN 61000-3-2, -3; EN 61000-4-2, -3, -4, -5, -6, -8, -11
© Tunstall GmbH, Orkotten 66, 48291 Telgte, Germany, www.tunstall.de, 00 8802 81, Rev. 7.0 (02/2017)
Product leaflets 03/2018, page 116
Order No.
00 0130 41
00 0132 02
00 0211 40
00 0211 41
00 0211 39
00 0211 20
00 0223 56
115 – 230 V AC
90 – 264 V AC
47 – 63 Hz
5.5 A at 115 V AC / 3 A at 230 V AC
12.5 A DC
24 V DC +/- 2%
26.5 – 19.5 V DC, typical
288 W
< 100 mV
eff
24 Ah
Typ. 3.0 A, temperature-dependent
approx. 1 hour
U
< 22.5 V, typical
a
21.5 V, typical
19.5 V, typical
EN 55022 Class B; ENV 50204
EN 60950
Safety Extra Low Voltage, SELV
3 kV
I
IP 20
0 ... +40°C
-25 ... +40°C
100,000 hours