Power supply unit UPS (77 3400 00)
9

Technical data

Input
Nominal voltage
Nominal voltage range
Input frequency
Output
Nominal current
Output voltage in mains operation
Output voltage in battery operation
Rated output power
Ripple for nominal output current
Battery capacity
Charging current
Bridging time for nominal current
Battery voltage thresholds
Switching threshold for UPS operation
Switching threshold for warning prior to battery
switch-off
Switching threshold for total discharge protection
EMC CE-certified
Safety
Output
Testing voltage PRI – SEC
Protection class
Degree of protection
General
Permissible ambient temperature in operation
Permissible ambient temperature
during storage and transport
MTBF
Power supply unit UPS (77 3400 00) – Instruction manual – 00 8802 41, 04/16 (Rev. 9.0)
115 - 230 V AC
90 - 264 V AC
47 - 63 Hz
12 A DC
24 V DC +/- 2%
Typ. 26.5 – 20 V DC
288 W
< 20 mVeff
7 Ah
Typ. 600 mA, temperature-dependent
Approx. 17 min
Ue < 92 V AC
Typ. 22 V
Typ. 20 V
EN 55022; EN 61000-3-2, -3;
EN 61000-4-2, -3, -4, -5, -6, -11
EN 60950-1
Safety Extra Low Voltage (SELV)
2 kV
Class I
IP 20
0 ... +40°C
-25 ... + 40°C (for optimum battery life:
cool and dry)
200,000 h ati 25°C (without batteries)