Power supply unit UPS (77 3400 00)
6.1.1
Output terminals (5) 24 V DC / 12 A
The power supply unit UPS provides a controlled output voltage of 24 V DC, max.
12 A.
If a load current of approximately 12 A is exceeded, the output voltage reduces at
a constant current according to the resistance value of the connected overload.
Connect the load to terminals "+24 V" and "0 V" (provided twice).
6.1.2
Signalling outputs (2) and LED displays (1)
The five signalling terminals (1 - 5) on the 7-pole terminal (2) use potential-free
relay contacts to indicate the device status. These contacts may be subjected to
a maximum load of 30 V DC/1 A.
LED lights up
Green,
"Output +24V DC"
Yellow,
"Battery active"
Yellow, "Battery
active" and
red, "Battery low"
Red, "Battery low"
(checked every 15
minutes)
Red,
"Output Failure
Fuse F2"
Tab.2: Signalling outputs and LED displays
1)
At an output voltage of around 20 V, the power supply unit UPS automatically
switches off completely (total discharge protection).
Power supply unit UPS (77 3400 00) – Instruction manual – 00 8802 41, 04/16 (Rev. 9.0)
Status
Output voltage
Mains operation
+24 V DC
Battery operation
+20 V
Battery empty
-
Battery defective
-
F2 failure. Output fuse
F2 has been removed
0 V
or is defective.
Product leaflets 03/2018, page 94
Connections and commissioning
Switched
contacts (NO)
3 – 5
1)
– 24 V DC
3 – 4
3 – 2
3 – 2
(checked every
15 minutes)
-