Pneumatic call switches, Order No. 77 0216 0x..., Installation Instructions
Setting a channel number (0–7)
If functional units are requested, the pneumatic call switches have to be assigned to different channels. Refer to your
installation plan to find out, whether channel numbers have to be assigned. Factory set to channel 0.
To set a channel number: Within the first ten seconds after the power supply is switched on, you have to start with the
procedure described in the following (Alternatively, the connector of the switch can be pulled off briefly and then re-
plugged):
1. Squeeze and keep squeezed the rubber bulb for approx. 5 seconds until the switch emits a beep and the upper
LED lights up pink.
ü The upper LED signals the current channel number:
Channel 0
= Upper LED flashes once in red.
Channel 1
= Upper LED flashes once in green.
Channel 2
= Upper LED flashes twice in green.
and so on ...
Channel 7
= Upper LED flashes seven times in green.
2. Set the channel number predefined in your installation plan as follows:
Channel 0
= Do not squeeze the rubber bulb.
Channel 1
= Squeeze the rubber bulb once.
Channel 2
= Squeeze the rubber bulb twice.
and so on ...
Channel 7
= Squeeze the rubber bulb seven times.
3. To save the setting squeeze and keep squeezed the rubber bulb until the switch emits a beep.
ü The new setting is saved.
Note! If you do not squeeze the rubber bulb within 30 seconds, the new setting is not saved.
ü The upper LED signals the set channel number:
Channel 0
= Upper LED flashes once in red.
Channel 1
= Upper LED flashes once in green.
Channel 2
= Upper LED flashes twice in green.
and so on ...
Channel 7
= Upper LED flashes seven times in green.
Setting the call type (if needed)
You can set the call type to be initiated by the switch.
- Pneumatic call switch, order no. 77 0216 00...; factory setting: Call. Optional setting: WC call.
- Pneumatic call switch/WC, order no. 77 0216 01...; factory setting: WC call. Optional setting: Call
To set the call type: Within the first ten seconds after the power supply is switched on, you have to start with the pro‐
cedure described in the following (Alternatively, the connector of the switch can be pulled off briefly and then re-
plugged):
1. Squeeze and keep squeezed the rubber bulb for approx. 10 seconds until the upper LED lights up white.
(Sequence: After approx. 5 seconds the switch emits a beep and the upper LED lights up pink. After a further
5 seconds the switch emits a second beep and the upper LED lights up white. Now release the rubber bulb.)
ü The upper LED signals the current setting for the call type:
Factory setting
Optional setting
2. Set the call type as follows:
Factory setting
Optional setting
3. To save the setting squeeze and keep squeezed the rubber bulb until the switch emits a beep.
ü The new setting is saved.
Note! If you do not squeeze the rubber bulb within 30 seconds, the new setting is not saved.
ü The upper LED signals the set call type:
Factory setting
Optional setting
00 8801 48, 05/15 (Rev. 3.0)
= Upper LED flashes once in red.
= Upper LED flashes once in green.
= Do not squeeze the rubber bulb.
= Squeeze the rubber bulb once.
= Upper LED flashes once in red.
= Upper LED flashes once in green.
Product leaflets 03/2018, page 20