14. Servicing
Functions
RAN interface with speech
Inspection interval: 3 months
 Is the connected call device undamaged
and free of contamination?
 Is a call triggered in the nurse call system
if the call device is triggered?
 Do the location and reassurance lights of
the call device work?
 Is a speech connection to the call device
established when a call is answered?
 Can both conversation partners hear at an
appropriate volume and understand each
other?
 Can the call be cancelled?
Telephone interface relay
Inspection interval: 3 months
 Is a call triggered in the nurse call system
when the connected telephone rings?
Smoke detector
Inspection interval: 3 months
 Is the housing undamaged and free of
contamination?
 Does the smoke detector trigger a call
within the nurse call system?
 Function test according to the provided
documentation of the manufacturer.
104
Order no.
77 0880 00
11 5350 00
77 0902 00
IP
Flamenco
- Technical Manual - 00 8813 52, 03/18 (Rev. 1.0)