Battery Set for UPS 60, Order No. 77 3450 00
4. Document the installation direction and connection polarity of the used batteries.
5. Remove the used batteries.
6. Insert the new batteries, using the same installation direction as the ones that have been
removed, and ensure that the connection polarity is correct. Reversing the polarity of the batteries
may result in the connected power supply unit UPS 60 being destroyed.
7. Put the rubber grommets back on the connection screws.
8. Fix the battery position by securing it with the Velcro tape.
9. Insert the battery fuse FKS 20A in the fuse holder.
10. Replace and close the housing.
11. Perform a functional check of the power supply unit UPS 60!
Disposing of batteries
Lead-acid AGM batteries contain harmful substances. These have the potential to damage the
environment and pose a risk to human health.
The bin icon means that these batteries must not be disposed of in household waste.
The "PB" designation under the bin indicates that the battery contains lead.
PB
End users are legally required to take used batteries to a suitable collecting depot.
If batteries are being disposed of in the Federal Republic of Germany, the Batteries Act (in the most
recent version of June 2012) must be observed. When disposing of batteries elsewhere in the EU,
refer to the national implementation of Directive 2006/66 EC that applies in each case. When
disposing of batteries in other economic regions, observe the regulations that apply in those cases.
5. Storage
If the battery set for UPS 60 will not be used for an extended period of time, the batteries must first be
fully recharged by the power supply unit UPS to preclude battery damage due to total discharging.
(Refer to item 4 Battery service life).
For the charging process, the power supply unit UPS shall be connected to the mains supply for at
least 4 hours, and the UPS function shall be activated by placing the bridging contact between "x"
and "y".
While the system is not used, the power supply unit UPS 60 must be disconnected from the
batteris of the battery set for UPS 60 to prevent total discharge.
6. Spare parts
Spare part
Rechargeable lead-acid battery, Type BAT 12-24 (2 batteries required)
Battery fuse, internal 20 A FKS
Clamp for battery connection, 2 pole
7. Technical data
Input
Nominal voltage
Output
Nominal current
Output voltage
Battery capacity
Safety
Output
Protection class
Ingress Protection
General
Permissible ambient temperature in operation
Permissible ambient temperature during
storage and transport
English - 4
Safety extra low voltage, SELV
(for optimum battery life: cool and dry)
© Tunstall GmbH, Orkotten 66, 48291 Telgte, Germany, www.tunstall.de, 00 8802 82, Rev. 5.0 (04/2016)
Product leaflets 03/2018, page 120
Order No.
00 0648 87
00 0132 03
00 0211 20
24 V DC
12.5 A DC
typ. 26.5 – 19.5 V DC
24 Ah
EN 60950
III
IP 20
0 ... +40°C
-25 ... +40°C