Pull cord call switches, Order No. 77 0215 0x...*), Installation Instructions
...*) The letter at the end of the order number represents the frame of the switch:
A = Frame dimensions (HxW): 91 x 91 mm, F = Frame dimensions (HxW): 80 x 80 mm
C = Frame dimensions (HxW): 107 x 107 mm. Caution! The frame C is made from real glass!
Note! The complete installation of the system is described in the Technical Manual.
Red LED
Red LED
Safety release
Pull cord
Call handle
Connecting the connector
Connect a 3-pole connector (order no. 70 0807 00) to the room
bus RAN (without speech) according to Fig. A.
Setting a channel number (0 – 7)
If functional units are requested, the pull cord call switches have to be assigned to different channels. Refer to your
installation plan to find out, whether channel numbers have to be assigned. Factory set to channel 0.
To set a channel number: Within the first ten seconds after the power supply is switched on, you have to start with the
procedure described in the following (Alternatively, the connector of the switch can be pulled off briefly and then re-
plugged):
1. Pull and keep pulled the cord for approx. 5 seconds until the switch emits a beep and the upper LED lights up pink.
ü The upper LED signals the current channel number:
Channel 0
= Upper LED flashes once in red (factory setting).
Channel 1
= Upper LED flashes once in green.
Channel 2
= Upper LED flashes twice in green.
and so on ...
Channel 7
= Upper LED flashes seven times in green.
2. Set the channel number predefined in your installation plan as follows:
Channel 0
= Do not pull the cord.
Channel 1
= Pull the cord once.
Channel 2
= Pull the cord twice.
and so on ...
Channel 7
= Pull the cord seven times.
3. To save the setting pull and keep pulled the pull cord until the switch emits a beep.
ü The new setting is saved.
Note! If you do not pull the cord within 30 seconds, the new setting is not saved.
ü The upper LED signals the set channel number:
Channel 0
= Upper LED flashes once in red.
Channel 1
= Upper LED flashes once in green.
Channel 2
= Upper LED flashes twice in green.
and so on ...
Channel 7
= Upper LED flashes seven times in green.
00 8801 47, 05/15 (Rev. 5.0)
Pull cord call switch, order no. 77 0215 00...*)
2,50 m pull cord and call handle for raising calls or WC calls (factory setting: calls).
The LEDs (red) are on with a weak light for finding the pull cord call switch in the
dark (night location light). The LEDs are on with a bright light, when a call was
raised (reassurance light).
The safety release opens, if the pulling force exceeds a limit value.
Pull cord call switch/WC, order no. 77 0215 01...*)
same as order no. 77 0215 00..., but factory setting: WC call.
3
Product leaflets 03/2018, page 17
B(lack) = 0 V
Y(ellow) = RAN
From a RAN user
R(ed) = +24V-Si
English
B
Y
R