8. Laying the cables
8.5.2
RAN room bus without speech (cable type Is)
Room devices that are used for speech transmission must be wired up with an addi-
tional speech line, i.e. 2x IY(ST)Y 2x2x0.8.
IY(ST)Y 2x2x0.8
IY(ST)Y 2x2x0.8
Fig. 11: RAN room bus with speech
The shield wire of the cable for speech transmission, i.e. the cable containing the
wires "MIC", "LS" and "SCH-B", is connected to the connection point "SCH-B".
Risk of malfunctions in the nurse call system!
The cable for speech transmission, i.e. the cable containing the wires "MIC",
"LS", and "SCH-B", may be stripped for a max. of 30 mm only, to ensure the pro-
tective screen function. Otherwise, a short circuit situation or crosstalk may oc-
cur.
The cable shield and the shield wire of the cable containing the wires "RAN",
"+24V-Si" and "0V" are not connected and must be removed in the back box up
to the cable sheath.
The unused wires must not be interconnected.
48
unused
white
yellow
RAN
+24V-Si
red
black
0V
MIC
white
yellow
LS
unused
red
black
SCH-B
max. 30 mm
Flamenco
ComTerminal