4. Interfaces
4.2

Interfaces at the ward

4.2.1
OSYlink-Universal
OSYlink-Universal
(77 0803 00)
Inputs and outputs
 4 monitored inputs:
- 2x Call
- Emergency call
- Cardiac alarm (code blue)
 1 input: collective announcement (all wards)
 1 input: collective announcement (all presences)
 1 input "Initiate call" and 1 associated input "Cancel call"
4 solid state outputs, configurable. Factory setting:
- 2x Call
- Emergency call
- Cardiac alarm (code blue)
 1 solid state output, can be configured
 1 output with location light function (functionally associated to the call inputs)
 2 potential free outputs, configurable (change-over contact, voltage source se-
lectable by jumper)
The outputs are configured centrally using the SystemOrganizer.
4.2.2
Connection of legacy systems
Flamenco
tured by Tunstall GmbH to the Flamenco
ward bus of the legacy system is connected to the Flamenco
through an OSYlink AS interface module. OSYlink AS is intended for installation into
ward distributors or installation rooms. Two different OSYlink AS interface modules
are available:
20
The interface OSYlink-Universal (77 0803 00) is
available as an interface for the connection of exter-
nal systems and/or technical equipment to the
group bus (OSYnet).
IP
provides the option of connecting wards with legacy systems manufac-
IP
nurse call system. For this purpose, the
IP
nurse call system
IP
Flamenco
- Technical Manual - 00 8813 52, 03/18 (Rev. 1.0)