WARNING! When laying the cables, closely observe the current rules!
8.1
Cable legend
To simplify the handling of installation plans, Tunstall GmbH has introduced an ex-
panded cable legend. The cables are organised according to their application areas.
Relevant types of cables are allocated to specific application areas. These shall be
considered as minimum requirements.
Marking
Ia
Ia2
Ia3
Ia4
Ia5
OSYnet
Ie
In
Ip
Is
Tab. 4: Cable legend
IP
Flamenco
- Technical Manual - 00 8813 52, 03/18 (Rev. 1.0)
8. Laying the cables
Designation
General cables
General cables
General cables
General cables
General cables
OSYnet group bus
Entertainment cables
RAN room bus
Power cable
Speech line plus RAN
room bus
Cable type
IY(ST)Y 2x2x0.8
IY(ST)Y 2x2x0.6
IY(ST)Y 3x2x0.6
IY(ST)Y 4x2x0.6
IY(ST)Y 4x2x0.8
Recommended cables:
CAT7 (22 AWG) with diameter = 0.64 mm
IY(ST)Y 4x2x0,8 with diameter = 0.8 mm
Optional cables:
CAT5 (23 AWG) with diameter = 0.57 mm
CAT6 (23 AWG) with diameter = 0.57 mm
CAT7 (23 AWG) with diameter = 0.57 mm
IY(ST)Y 4x2x0,6 with diameter = 0.6 mm
2x IYY per channel
or similar cables (1 double wire required
for each programme)
IY(ST)Y 2x2x0.8
NYM 2x2.5 mm²
2x IY(ST)Y 2x2x0.8