CO Alarm Operation

Third line in display: Z000 indicates the zone programmed to this device which, in this example, is general alarm Zone 000. Note that a
single device can be programmed to five different zones but only the first zone will be displayed.
Fourth line in display:
Time; the current time in this example is 02:37P which represents 2:37 PM
Date; the current month, day and year in this example is 06 for June, 25 for the 25th day of the month and 22 for the year 2022
Device Address; 1M001 in this example 1 represents SLC Loop, M represents a module and 001 represents device address 001
4.6 CO Alarm Operation
NOTE: When using carbon monoxide detection the system must be monitored by a Supervising Station, meeting the Standard for the
Installation of Carbon Monoxide (CO) Detection and Warning Equipment, NFPA 720.
When a CO alarm operation occurs:
The piezo sounder produces a steady Temporal 4 output
The CO Alarm LED flashes 1 second On and 1 second Off
The LCD displays CO Alarm along with the device name, type, address, adjective/noun, associated zones and time/date
Communicate the CO alarm to the Central Station
CO alarms latch and are not allowed to clear automatically
CO alarms activate software zones if so programmed
Timers for Silence Inhibit, Autosilence, and Alarm Reminder are started
CO alarms activate the relays programmed for CO alarm
The trouble relay is not activated
Store event in history buffer
Terminate upload or download communications
CO alarms must be Acknowledged before the FACP can be reset
A typical CO alarm display would be as illustrated below:
The information displayed in the above example provides the following information:
First line in display:
The type of event; in this example ALARM indicating a CO alarm condition
Device type identifier; in this example, CAR MONOXIDE indicates a CO detector.
Second line in display:
<ADJ>; refers to the user programmed adjective descriptor from library list resident in the control panel or custom entry via PC.
<NOUN>; refers to the user programmed noun descriptor from library list resident in the control panel or custom entry via PC.
Third line in display: Z002 indicates the zone programmed to this device which, in this example, is general alarm Zone 002. Note that a
single device can be programmed to five different zones but only the first zone will be displayed.
Fourth line in display:
Time; the current time in this example is 11:46P which represents 11:46 PM
Date; the current month, day and year in this example is 10 for October, 09 for the 9th day of the month and 22 for the year 2022
Device Address; 1M001 in this example 1 represents SLC Loop, M represents a module and 001 represents device address 001

4.7 Supervisory Operation

Supervisory operation is similar to alarm operation but with the following differences:
The piezo sounder pulses ½ second On and ½ second Off
The Supervisory LED flashes ½ second On and ½ second Off
The LCD displays the status label Active Supervisory along with the device name, type, address, adjective/noun, associated zones, and
time/date
Communicate the supervisory condition to the Central Station
The supervisory relay is activated
The alarm relay is not activated
Silenced alarms are resounded
Timers are not started
Store event in history buffer
Terminate upload or download communications
ES-1000X Series Manual — P/N LS10133-000FL-E:A 6/21/2023
ALARM CAR MONOXIDE
<ADJ> <NOUN>