Festo CPX-CM-HPP Electronic Manual page 76

Cpx terminal, fhpp interface.
Hide thumbs Also See for CPX-CM-HPP:
Table of Contents

Advertisement

4. Diagnosis and error treatment
st
nd
1
position
2
Axis no.
Mode/
error no.
1
2
3
4
in
Initialisation
S
Record
Record
selection
d
Direct mode
Direct mode
E
Error
12
u
Warning
28
Tab. 4/3: Information on the three−digit 7−segment display
4−12
The following table describes the significance of the
individual positions of the 7−segment display.
rd
position
3
position
Status/
error no.
0
1
2
0
1
2
Significance
Display of the status of the x−axis
Display of the status of the y−axis
Display of the status of the z−axis
Display of the status of the u−axis
Initialization display
Connection set−up and initialization of the axes
one after the other. Only when initialization of the
current axis has been successfully completed will
initialization of the next axis be started.
Axis is switched on (Axis is READY)
Controller enable (Axis is ENABLED)
Axis is homed (Axis is REFERENCED)
Axis is switched on (Axis is READY)
Controller enable (Axis is ENABLED)
Axis is homed (Axis is REFERENCED)
Error no.: 12
The display first shows E" and then 12".
Warning: 28
The display first shows u" and then 28".