Festo CPX-CM-HPP Electronic Manual page 58

Cpx terminal, fhpp interface.
Hide thumbs Also See for CPX-CM-HPP:
Table of Contents

Advertisement

3. Commissioning
3−22
Value
Format
2
BD/AD [mm]
Tab. 3/10: Configuration parameter Format
Two words are used when a controller with an address
range > 65536 is used. A conversion into hexadecimal values
is required; see following example:
245987 = 0x3C0E3
Byte 4.5 (FHPP): 0xC0E3
Byte 6.7 (FHPP): 0x0003
Conversion is not necessary when a higher−level fieldbus
master and double words are used.
If a Profibus control is used, attention must be paid that the
bytes are correctly transferred. The bytes might be
transposed.
Significance
If a 16−bit controller is used, e.g. CPX−FEC:
for MTR−DCI and SFC−xx, the position
value is first converted into [ m] or
[1/1000°] and then into before decimal
word (BD) and after decimal word (AD).
Position
Position
value
value
[ m] or
[mm] or
[1/1000 °]
[°]
245987
245,987
1234034
1234,034
200065
200,065
345
0,345
Festo P.BE−CPX−CM−HPP−EN en 0910NH
BD
AD
245
987
1234
34
200
65
0
345