Electrical Tests

Standards
Standards:
Insulation Test according to IEC EN 61010-1 and IEC EN 61010-2-030
Inputs/Outputs
Current measurement inputs
Voltage measurement inputs
Supply voltage
Binary outputs
Ethernet interface
EMC Tests for Immunity (Type Tests)
Standards:
Electrostatic discharge, Class III,
IEC 61000-4-2
High frequency electromagnetic field, amplitude-modulated,
Class III
IEC 61000-4-3
Fast transient bursts, Class III
IEC 61000-4-4
High energy surge voltages (SURGE), Installation Class III
IEC 61000-4-5
Line-conducted high frequencies, amplitude-modulated, Class
III
IEC 61000-4-6
Power system frequency magnetic field
IEC 61000-4-8, Class IV;
1 MHz test, Class III, IEC 61000-4-18
SENTRON PAC5100/5200, 7KM5212/5412, Device Manual
E50417-H1040-C568-A1, Edition 03.2015
Insulation
Reinforced
Reinforced
Reinforced
Reinforced
Function
Auxiliary voltage
Measuring inputs, binary inputs, and
relay outputs
IEC EN 61000-6-2
IEC EN 61000-6-4
IEC EN 61010-1
IEC EN 61010-2-030
Rated
ISO Test Voltage
Voltage
150 V
AC 2.3 kV
480 V
Surge voltage
9.76 kV
300 V
DC 3.125 kV
300 V
AC 3.536 kV
< 50 V
DC 700 V
IEC EN 61000-6-2
For more standards see also individual
functions
6 kV contact discharge; 8 kV air discharge,
both polarities; 150 pF; R
with connected Ethernet cable
10 V/m; 80 MHz to 3 GHz; 80 % AM; 1 kHz
2 kV; 5 ns/50 ns; 5 kHz;
Burst length = 15 ms;
Repetition rate 300 ms;
Both polarities;
R
= 50 ;
i
Test duration 1 min
Impulse: 1.2 µs/50 µs
Common mode: 2 kV; 12 ; 9 µF
Diff. mode:1 kV; 2 ; 18 µF
Common mode: 2 kV; 42 ; 0.5 µF
Diff. mode: 1 kV; 42 ; 0,5 µF
10 V; 150 kHz to 80 MHz; 80 % AM; 1 kHz
30 A/m continuous; 300 A/m for 3 s
2.5 kV (peak); 1 MHz;  = 15 µs;
400 Surges per s;
Test duration 1 min; R
12 Technical Data
12.2 Test Data
Category
Cat. III
Cat. III
Cat. III
Cat. III
Cat. III
= 330 
i
= 200 