7 Operation at Use of a PC
7.6 Example of a Parameterization and Measured Value Evaluation for SENTRON PAC5200
On the Configure tab, Recording parameters item (see Recording Parameters) select Start
immediately.
Figure 7-80
Go to the Configure tab, Save configuration to file menu item to save your device configuration as the
active parameter set as described in Save Configuration to File.
Enable the active parameter set in the device as described in Activating the Set of Parameters.
NOTE
After changing the network settings and subsequent parameter activation the device will reset.
7.6.4

Performing the Measurement

Switch on the rated voltages and rated currents at the measuring inputs E and F of SENTRON PAC5200
observing the safety notes given in Commissioning.
Read the measured values from the Value view and Evaluation tab by calling the Operational
parameters, Harmonics, AC power and energy, Binary outputs and Limits menu items according to
Value View and Evaluation in the navigation window.
The user interface displays the status of binary output G1/3 which corresponds to the parameterized
indication Vab_>11kV.
If the parameterized limit of the voltage Vab is exceeded, a corresponding limit violation indication is
displayed in the table.
NOTE
Measured values and indications are refreshed after 5 s on the Value view and Evaluation tab.
Display the power quality events and the memory utilization on the Value view and Evaluation tab.
190
Configure Tab, Start Immediately Example
SENTRON PAC5100/5200, 7KM5212/5412, Device Manual
E50417-H1040-C568-A1, Edition 03.2015