7 Operation at Use of a PC
7.3 Configuration of the Device
Parameterizing a Limit
To change, for example, limit 1, proceed as follows:
In the navigation window, select the Operational menu, then the Select automation functions submenu
and click Measurand limits 1-8.
Figure 7-28
Enter the desired values in the fields and select the parameters in the list boxes and option fields as
described in Table 7-6.
Hysteresis of the Limit Value Violation
100 %
Limit Max
Limit Min
0 %
Figure 7-29
NOTE
Select Measurand -none- to disable the corresponding measurand limit indication.
126
Configure Tab, Measurand Limits 1-8 Input/Output Window (Detail)
Permissible
Start
End
Start
Hysteresis (General Representation)
Hysteresis range
range
t
End
SENTRON PAC5100/5200, 7KM5212/5412, Device Manual