7.3.6.2 Communication Ethernet
Default Settings and Setting Ranges of the Communication Ethernet
Table 7-18
1)
IP address
Subnet mask
Default gateway
Enable SNMP
Bus protocol
Bus Protocol Modbus TCP
Use a user-port number
User-port number
(can only be set when Use a user-port
number is parameterized with yes)
Access rights for user port
(can only be set when Use a user-port
number is parameterized with yes)
Access rights for port 502
Keep Alive time
Communication supervision time
1)
After the parameter changes have been enabled, the device will reset.
2)
After enabling the parameter changes, any currently active Modbus TCP connections will be closed. The
Modbus TCP client must later reopen these connections.
SENTRON PAC5100/5200, 7KM5212/5412, Device Manual
E50417-H1040-C568-A1, Edition 03.2015
Communication Ethernet Settings
Parameter
1)
1)
2)
2)
Default Setting
192.168.0.55
255.255.255.0
192.168.0.1
no
Modbus TCP
no
10000
Full
Full
10 s
600 * 100 ms
7 Operation at Use of a PC
7.3 Configuration of the Device
Setting Range
Any
0.0.0.0 = DHCP
Any
Any
no
yes
-none-
Modbus TCP
no
yes
10000 to 65535
Full
Read only
Full
Read only
0 s = switch off
1 s to 65 535 s
0 s = none
100 ms to 6 553 400 ms
151