7.3.3.2 Automation Functions
7.3.3.2.1
Limit Settings
In the Select automation functions menu you can set upper or lower limits for up to 16 measured values.
Limit violations of the upper or lower value range can be output as indications. Up to 4 limiting value violations
can be signaled at the device via the two binary outputs and the LEDs H1 and H2. Furthermore, all 16 limit
violations can be sent to peripheral devices via Ethernet.
The programmable limits are divided into two groups Limits 1-8 and Limits 9-16. The parameterization is
identical for all limits.
Default Settings and Setting Ranges of the Limits
Table 7-6
Parameter
Measurand
Limit
Limit type
Hysteresis (%)
Violation indication
SENTRON PAC5100/5200, 7KM5212/5412, Device Manual
E50417-H1040-C568-A1, Edition 03.2015
Limit Settings
Default Setting
-none-
0.0
Lower
1.0
Limit Violation x
(x = 1 to 16)
7 Operation at Use of a PC
7.3 Configuration of the Device
Setting Range
Acc. to list box
(see Operating Parameters)
-1 000 000 000 to 1 000 000 000 (unit)
Lower
Upper
0.0 to 10.0
The name of the limit violation indication is
customizable.