9810 Specifications; Mechanical Characteristics; Mechanical Compliance; Electrical Characteristics - Siemens US2:9810T24V User Manual

Table of Contents

Advertisement

9810 specifications

9810 specifications
This section provides additional specifications for your meter and accessories.
NOTE: The information contained in this section is subject to change without notice. You can
download updated documentation from www.usa.siemens.com/pds or contact your local
Siemens Industry representative for the latest updates.

Mechanical characteristics

9810 series meter
Mounting options
Orientation
IP degree of protection
Maximum number of option
modules

Mechanical compliance

Vibration
Shock

Electrical characteristics

Measurement accuracy
Active energy (Wh)
Reactive energy (VARh)
Power monitoring device (PMD) IEC 61557-12 PMD/SD/K70/0.2 and PMD/SS/K70/0.2
Active power (P)
Reactive power (Q
Apparent power (S
Apparent energy (E
Current (I)
Voltage (U)
Frequency (f)
291
DIN rail: IEC 60715 (DIN EN 60715), TH 35–7.5 or TH 35–15
Panel mount: with 9810BBADAPTER
Vertical, retaining clips located on bottom of meter
IP30 (except connectors)
4 (based on maximum operating temperature)
IEC 60068-2-6
IEC 60068-2-57
IEC 60068-2-27
IEC 60068-2-31, Test Ec Free fall procedure 1
IEC 62053-22 Class 0.1 S
IEC 62053-24 Class 0.5 S
IEC 61557-12 Class 0.1
)
IEC 61557-12 Class 1
V
)
IEC 61557-12 Class 0.2
V
)
IEC 61557-12 Class 0.2
apV
IEC 61557-12 Class 0.1
IEC 61557-12 Class 0.1
IEC 61557-12 Class 0.02
9810 series - User manual