14 Operating Parameters
14.2 Automation Functions
14.2
Automation Functions
The following automation functions are available:
•
Limit violation 1-8
•
Limit violation 9-16
•
Group indication 1-4
14.2.1
Limit Violation 1-8 and 9-16
Parameter
Measurand
Limit
Limit type
Hysteresis (%)
Violation indication
248
Default Setting
-none-
0.00
Lower
1.0
Limit Violation x
(x = 1 to 16)
SENTRON PAC5100/5200, 7KM5212/5412, Device Manual
Setting Range
-none-
Va; Vb; Vc
Vab; Vbc; Vca
Ia; Ib; Ic
VN; Vavg
IN; Iavg
Pa; Pb; Pc; P
Qa; Qb; Qc; Q
Sa; Sb; Sc; S
cos (a); cos (b); cos (c); cos
PFa; PFb; PFc; PF
UIa; UIb; UIc; UI
f
U
2
Iunbal
THDS Va, THDS Vb, THDS Vc
THDS Ia, THDS Ib, THDS Ic
ab V, ca V
ab I, ca I
Q1a, Q1b, Q1c; Q1
Pinst (a-n), Pinst (b-n),Pinst (c-n)
Pst (a-n), Pst (b-n),Pst (c-n)
Plt (a-n), Plt (b-n),Plt (c-n)
Pinst (a-b), Pinst (b-c),Pinst (c-a)
Pst (a-b), Pst (b-c),Pst (c-a)
Plt (a-b), Plt (b-c),Plt (c-a)
(Setting ranges pending from network type)
-1 000 000 000 to 1 000 000 000 (unit)
Lower
Upper
0.0 to 10.0
The name of the limiting value indication is
customizable.
E50417-H1040-C568-A1, Edition 03.2015