Siemens SENTRON PAC5200 Device Manual page 241

Power monitoring device and power quality recorder
Table of Contents

Advertisement

Indication
Rotating Field Clock-
wise
Group indication x
Supply Voltage Event
Available
Frequency Event
Available
Volt. Unbalance
Event Available
PQ Event
SD Card Error
1)
The SD card has no contact or is defective; you must not replace the card yourself. The device also works
without active SD card. However, data storage when operating the recorders is not possible. In this case,
the recorder data can be forwarded and processed only via communication.
SENTRON PAC5100/5200, 7KM5212/5412, Device Manual
E50417-H1040-C568-A1, Edition 03.2015
Description
Indication of rotation voltage
Up to 4 single-point indications can
be linked logically and combined to
a group indication.
Indication of a supply voltage event
Indication of a frequency event
Indication of a voltage unbalance
event
Indication of a fault recorder event
Indication of an SD card error
Notes
Indication ON: Phase sequence Va-Vb-Vc, rotation
clockwise
Indication OFF: Phase sequence Va-Vc-Vb, (2 phases
interchanged); rotation anti-clockwise
Indication invalid: Direction of rotation can not calculated
(e.g. no voltage applied)
A total of 4 group indications (x = 1 to 4) can be param-
eterized.
Overvoltage, undervoltage, frequency interruption
Overfrequency or underfrequency
Voltage unbalance
A fault record was recorded.
SD card defective or read/write error