7 Operation at Use of a PC
7.3 Configuration of the Device
7.3.3.1 Process Connections
7.3.3.1.1
AC Measurement
Default Settings and Setting Ranges of Measured-value Acquisition
NOTE
When setting the parameters, make sure that the set values are not contradictory.
In the case of contradictory parameter settings, Primary nominal voltage is indicated as faulty (red) and Net-
work type as not adjustable (gray). Moreover, the Send button is disabled.
If the settings of the Voltage transformer (primary rated voltage and secondary rated voltage) are invalid (red)
referred to the Network type and Primary nominal voltage of the network, they are not adjustable either
(gray). The Send button is disabled. An entry is added in Error log message logs.
Table 7-2
Settings for Measured-value Acquisition
Parameter
Rated frequency
Network type
Primary nominal voltage
Voltage transformer
At voltage transformer: yes
Primary rated voltage
Secondary rated voltage
Voltage measurement range
Current measurement range
Current transformer
At current transformer: yes
Primary rated current
Secondary rated current
Zero-point suppression
Voltage harmonic unit
1)
Voltage and current values smaller than/equal to the setting referred to 100 % are not included in the
calculation and display.
116
Default Setting
50 Hz
Four-wire, 3-phase, unbalanced
AC 400.00 V
no
AC 400.00 V
AC 400.00 V
ph-N: AC 400 V
(inject a maximum of AC 347 V for UL)
ph-ph: AC 690 V
(inject a maximum of AC 600 V for UL)
AC 5 A
no
AC 1000.00 A
AC 1.00 A
1)
0.3 % (from Vrated, Irated)
%
Setting 50 Hz: 50 Hz ±7.5 Hz
Setting 60 Hz: 60 Hz ±9 Hz
Acc. to list box
(see Operating Parameters)
AC 1 V to AC 1 000 000 V,
dependent on the setting range
in the selected network type
(see table 7-3)
yes
no
AC 100.00 V to 1 000 000.00 V
AC 1.0 V to 1000.0 V
Acc. to list box
(see Operating Parameters)
AC 1 A
AC 5 A
yes
no
AC 1.00 A to 100 000.00 A
AC 0.01 A to 10.00 A
0.0 % to 10.0 %
%
V
SENTRON PAC5100/5200, 7KM5212/5412, Device Manual
E50417-H1040-C568-A1, Edition 03.2015
Setting Range