Recording And Reporting; Event Recorders; Trigger Management - Siemens SENTRON PAC5200 Device Manual

Power monitoring device and power quality recorder
Table of Contents

Advertisement

14 Operating Parameters

14.4 Recording and Reporting

14.4
Recording and Reporting
14.4.1

Event Recorders

Parameter
Swell threshold
Dip threshold
Interruption threshold
Event hysteresis
Underfrequency threshold
Overfrequency threshold
Voltage unbalance threshold
14.4.2

Trigger Management

Parameter
Trigger active
Tolerance unit
Lower threshold
Upper threshold
252
Default Setting
Supply Voltage
110 %
90 %
5 %
2 %
Frequency
1 %
1 %
Unbalance
5 %
Default Setting
Voltage trigger limits
no
Percentage
90.00 %
of the of the primary nominal
voltage
110.00 %
of the of the primary nominal
voltage
SENTRON PAC5100/5200, 7KM5212/5412, Device Manual
Setting Range
105 % to 140 % in 5-% steps
75 % to 95 % in 5-% steps
1 %, 2 %, 3 %, 5 %, 8 % 10 %
1 % to 6 % in 1-% steps
0.1 % to 0.9 % in 0.1-% steps
1 % to 5 % in 1-% steps
0.1 % to 0.9 % in 0.1-% steps
1 % to 5 % in 1-% steps
1 % to 5 % in 1-% steps
Setting Range
no
yes
Percentage
Numerical
0.00 % to 99.99 % of the of the primary
nominal voltage
0.0 V to 1 000 000.0 V
100.0 % to 10 000.0 % of the primary
nominal voltage
0.0 V to 1 000 000.0 V
E50417-H1040-C568-A1, Edition 03.2015