Table 8-3
Parameter
Connection type
Rated value
Use PTs?
Use PTs:
V primary
Primary rated voltage Ph-Ph
Use PTs:
V secondary
Secondary rated voltage Ph-
Ph
Rated value
Use CTs?
Use CTs:
I primary
primary rated current
Use CTs:
I secondary
secondary rated current
Zero-point suppression
(in % of Vrated
and Irated)
SENTRON PAC5100/5200, 7KM5212/5412, Device Manual
E50417-H1040-C568-A1, Edition 03.2015
Basic Parameter Settings
Default Setting
The connection type is indicated on the display. However, it can be set via
the User interface only.
The rated value is indicated on the display. However, it can be set via the
User interface only.
No
(no checkmark)
AC 10,000.00 V
AC 100 V
AC 5 A
No
(no checkmark)
AC 1,000.00 A
AC 1.00 A
0.3 %
Voltage Inputs
Yes (checkmark)
No (no checkmark)
AC 100.00 V to 1,000,000.00 V
AC 1.0 V to 1000.0 V
Current Inputs
AC 1 A
AC 5 A
Yes (checkmark)
No (no checkmark)
AC 1.0 A to 100,000.0 A
AC 0.01 A to 10 A
Zero-Point Suppression
0.0 % to 10.0 %
8 Operation at Use of the Display
8.4 Parameterization
Setting Range
203