Inputs And Outputs - Siemens SENTRON PAC5200 Device Manual

Power monitoring device and power quality recorder
Table of Contents

Advertisement

12.1.2

Inputs and Outputs

Inputs for Alternating Voltage Measurements (Connector Block F)
Rated input alternating voltages
Phase-N/PE
Phase-phase
Maximum input alternating voltage (depending on the
parameterization)
Maximum input alternating voltage
Phase-N/PE
Phase-phase
Input impedances
a, b, c to N
a-b, b-c, c-a
Further information about the voltage measuring inputs
Power consumption per input for V
Permissible power frequency
Measuring error (with calibration) at 23 °C ± 1 °C
50 Hz or 60 Hz
SENTRON PAC5100/5200, 7KM5212/5412, Device Manual
E50417-H1040-C568-A1, Edition 03.2015
63.5 V
110 V
230 V
400 V (347 V for UL conditions)
110 V
190 V
400 V
690 V (600 V for UL conditions)
1.2 x rated input alternating voltage
480 V (347 V for UL conditions)
831 V (600 V for UL conditions)
6.0 M
6.0 M
400 V
38 mW
rated
42.5 Hz to 69.0 Hz
typically 0.1 % for reference conditions
12 Technical Data
12.1 General Device Data
229

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Sentron pac5100

Table of Contents