Take the wrapped battery out of the battery compartment.
Remove the plastic foil from the battery.
Insert the battery into the battery compartment with the polarity imprinted on the top side of the device (see
Figure 5-1).
Close the cover of the battery compartment.
Replacing a Used Battery
WARNING
Warning of incorrect treatment of the lithium battery (type PANASONIC CR2032 or VARTA 6032 101 501) or
the use of an incorrect battery type. In the case of incorrect treatment or the wrong battery type, the battery
may burn, explode or trigger a chemical reaction.
Non-observance may lead to death or serious injury.
Installing the battery or replacing it may only be carried out by trained personnel (see preface) who are
familiar with and observe the safety requirements and precautions.
Do not reverse the polarity of the battery.
Do not attempt to open the battery.
Do not attempt to recharge the battery.
Servicing of the circuitry involving the batteries and replacement of the lithium batteries shall be done by
a trained technician.
Replace battery with VARTA 6032 101 501 or PANASONIC CR2032 only. Use of another battery may
present a risk of fire or explosion. See manual for safety instructions.
Caution: The battery used in this device may present a fire or chemical burn hazard if mistreated. Do not
recharge, disassemble, heat above 100 °C (212 °F) or incinerate.
Dispose of used battery promptly. Keep away from children.
Replace the batteries if the battery charge is too low (avoid full discharge). In this case the "Battery Failure"
operation indication is generated. This message can also be parameterized on one of the three LEDs H1/H2/
ERROR or switched to one of the binary outputs.
When the "Battery Failure" indication is displayed, replace the battery as follows:
Lever the cover of the battery compartment out of the socket with a suitable tool (e.g. precision engineer
screwdriver 2.0 mm).
Use an appropriate non-conducting tool (for example plastic tweezers) to pull the battery out of the
compartment.
Remove the new battery type PANASONIC CR2032 or VARTA 6032 101 501 from the packaging (check
the expiry date on the packaging)
Insert the battery carefully into the battery compartment with the polarity indicated above the battery
compartment.
Press the cover of the battery compartment back into the housing and make sure it is in the correct
position.
SENTRON PAC5100/5200, 7KM5212/5412, Device Manual
E50417-H1040-C568-A1, Edition 03.2015
5.1 Unpacking, Inspecting the Delivery, and Installing the Battery
5 Getting Started
69

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Sentron pac5100

Table of Contents