To change the parameters of the measured-value acquisition, proceed as follows:
In the navigation window, select the Operational menu, then the Process connections submenu and
click AC measurement.
Figure 7-20
Enter the desired values in the fields and select the parameters in the list boxes and option fields as
described in Table 7-2.
Dependent on the parameterized Primary nominal voltage, the following Voltage measurement
ranges are set automatically and the following network types are possible:
Table 7-3
Primary Nominal
AC 230 V
AC 380 V
(> AC 230 V * 1.2)
> AC 480 V
(> AC 400 V * 1.2)
SENTRON PAC5100/5200, 7KM5212/5412, Device Manual
E50417-H1040-C568-A1, Edition 03.2015
Configure Tab, AC Measurement Input/Output Window
Settings for Primary Nominal Voltage
Selection of the Voltage Measurement Range
Voltage
ph-N: 230 V, ph-ph: 400 V
All other voltage measurement ranges are disabled.
ph-N: 400 V, ph-ph: 690 V
All other voltage measurement ranges are disabled.
ph-N: 400 V, ph-ph: 690 V
All other voltage measurement ranges are disabled.
7 Operation at Use of a PC
7.3 Configuration of the Device
Selectable
Network Types
all
all
all three-wire
network types
117