en | Central Console, computer setup and programming
1.
2.
3.
4.
2017.08 | V2.18.1.0 | DOC
Turn on the power switch on the first transponder. In the Security Escort Central Console
software, select the menu Setup > Transponder current status. The following dialog
window appears:
Select the desired transponder. Click the [Reset Transponder Troubles] button. If the
selected transponder is communicating with the Central Console, the number "1" will
appear in the Total Outgoing Messages and Successful Incoming Messages fields. The
transponder is now communicating with the Central Console software. If the number "1"
only appeared in the Total Outgoing Messages field, there is a wiring problem between
the Central Console and the transponder (refer to Troubleshooting reference, page 97 of
this manual and locate the problem).
Check the Stress test checkbox. This tests the communications reliability by causing the
Central Console software to send a continuous stream of messages to the selected
transponder. The values in the Successful Incoming Messages and Total Outgoing
Messages fields should start counting up rapidly, with few if any errors. It is normal to
have slightly fewer Total Outgoing Messages than Successful Incoming Messages. If the
errors are greater than 1% of the number of messages, then there is a problem that
should be corrected (refer to Troubleshooting transponders, points, receivers, and alert
units, page 93 of this manual and locate the problem).
After the stress test runs, any current troubles are displayed in the box in the
Transponder current status window. Correct any troubles at this time.
Training Manual
Security Escort
Robert Bosch (SEA) Pte Ltd