Bosch Security Escort SE2000 Series Training Manual page 121

Hide thumbs Also See for Security Escort SE2000 Series:
Table of Contents

Advertisement

Security Escort
Recall operator in 'X'
seconds
On outside tests, flash
strobe for 'X' seconds
Man down delay timer 'X'
seconds
Man down jitter timer 'X'
seconds
Auto Reset Comm Ports 'X'
hours
Trigger all the outputs on
alarm 'X' seconds
End of shift reminder
First, Second, Third shift
reminder
Robert Bosch (SEA) Pte Ltd
Troubleshooting transponders, points, receivers, and alert units | en 121
This box determines the length of time before a recall alert is
issued to the operator at the Central Console when an alarm is
being displayed. If neither the mouse nor any key has been
actuated for the specified length of time, the Central Console
will trigger the alarm sound once. This feature prevents
inadvertently ignoring an active alarm event. The numerical value
is in seconds, and it can be set between 0 and 240. Typically this
would be set to 60 seconds.
The entry in this box controls the approximate length of time the
strobe on an alert unit will flash to signify a successful
transmitter test. The value is in seconds, and can be set between
0 and 15. Typically it is set to 5 seconds.
This value controls the time that a transmitter must be in a man
down condition before a man down alarm is displayed. Typically
it would be set to 10 seconds. Setting this value too short will
cause inadvertent man down alarms to be generated.
This value controls the time that a transmitter will not be
considering any man down alarm if man down alarm is received
immediately after restore and before jitter time expire. This
setting will not be used in normal system.
This value controls the time that all the comm ports in the
system will be automatically reset after configured duration. This
setting is used only if any communication failure is observed and
should not be used unnecessarily.
This option turns on all outputs of the transponders, and alert
units for the duration configured (1-255 seconds) when alarm is
generated. If someone acknowledges an alarm during this
duration, all these outputs will be turned off. Otherwise, after
this duration has lapsed, all these outputs will be turned off
automatically. If this value is set to 0, the system will trigger the
outputs during alarms in the default normal behavior.
A check in this checkbox causes a prompt to appear on the
Central Console screen every 5 minutes for 30 minutes prior to
the end of each shift if there are incident reports that have not
yet been completed. It is intended for responding officers to
complete alarm reports before the end of their shift.
The entries in these fields are the times (24-hour clock) at which
the Central Console will prompt the operator that there is one or
more incident reports that have not yet been completed.
Prompts will be given only if the End of Shift Reminder option is
selected.