134 en | Troubleshooting transponders, points, receivers, and alert units
Enable reed switch
Optional text
Disable on shorted loop If selected, a shorted loop on this transmitter will not cause an alarm
Alarm on shorted loop If selected and the alarm group, where this transmitter is assigned
Trouble on shorted loop If selected, a shorted loop on this transmitter will cause a trouble
Alarm when armed,
Trouble when disarmed
on shorted loop
Disable open loop
Alarm on open loop
Trouble on open loop
2017.08 | V2.18.1.0 | DOC
If checked the reed switch input of this transmitter enabled to cause
an alarm. Otherwise the reed switch input will be disabled. The alarm
group this transmitter is assigned to must be armed, for this input to
cause an alarm, which is displayed. If no alarm group is assigned, the
transmitter is always armed. For this option to be enabled, the
transmitter's class must be set to "Point type".
This is optional text that will be added to the location text when this
input reports an alarm. For this option to be enabled, the
transmitter's class must be set to "Point type".
or trouble report to be displayed. For this option to be enabled, the
transmitter's class must be set to "Point type".
to, is armed, then a shorted loop on this transmitter will cause an
alarm report to be displayed. The alarm group this transmitter is
assigned to must be armed, for this input to cause an alarm, which is
displayed. If no alarm group is assigned, the transmitter is always
armed. For this option to be enabled, the transmitter's class must be
set to "Point type".
report to be displayed. For this option to be enabled, the
transmitter's class must be set to "Point type".
If selected and the alarm group, where this transmitter is assigned
to, is armed; then a shorted loop on this transmitter will cause an
alarm report to be displayed. If selected and the alarm group, where
this transmitter is assigned to, is disarmed, then a shorted loop on
this transmitter will cause a trouble report to be displayed. If no
alarm group is assigned, the transmitter is always armed. For this
option to be enabled, the transmitter's class must be set to "Point
type".
If selected, an open loop on this transmitter will not cause an alarm
or trouble report to be displayed. For this option to be enabled, the
transmitter's class must be set to "Point type".
If selected and the alarm group, where this transmitter is assigned
to, is armed, then an open loop on this transmitter will cause an
alarm report to be displayed. The alarm group, where this transmitter
is assigned to, must be armed for this input to cause an alarm, which
is displayed. If no alarm group is assigned, the transmitter is always
armed. For this option to be enabled, the transmitter's class must be
set to "Point type".
If selected, an open loop on this transmitter will cause a trouble
report to be displayed. For this option to be enabled, the
transmitter's class must be set to "Point type".