5.11 INPut Group
[:INPut]:SCALing:{VT|CT|SFACtor}:{SI
GMA|SIGMB|SIGMC}
Function
Collectively sets the VT ratio, CT ratio, or power
coefficient of all the elements that belong to the
specified wiring unit (ΣA, ΣB, or ΣC).
[:INPut]:SCALing:{VT|CT|SFACtor}:
Syntax
{SIGMA|SIGMB|SIGMC} {<NRf>}
<NRf> = 0.0001 to 99999.9999
Example
:INPUT:SCALING:VT:SIGMA 1
Description SIGMA, SIGMB, or SIGMC is invalid if the wiring
system setting ([:INPut]:WIRing) is made in such
a way that the corresponding wiring unit (ΣA, ΣB,
or ΣC) does not exist.
[:INPut]:SYNChronize?
Function
Queries the synchronization sources of all
elements.
[:INPut]:SYNChronize?
Syntax
[:INPut]:SYNChronize[:ALL]
Function
Collectively sets the synchronization source of all
elements.
[:INPut]:SYNChronize[:ALL] {U<x>|
Syntax
I<x>|EXTernal|Z1|Z3|NONE}
<x> = 1 to 7 (element)
EXTernal = External clock input (Ext Clk)
Z1 = Z Phase1 (ChD) (/MTR1 option required)
Z3 = Z Phase3 (ChH) (/MTR2 option required)
NONE = No synchronization source
:INPUT:SYNCHRONIZE:ALL I1
Example
[:INPut]:SYNChronize:ELEMent<x>
Function
Sets or queries the synchronization source of the
specified element.
[:INPut]:SYNChronize:
Syntax
ELEMent<x> {U<x>|I<x>|EXTernal|Z1|
Z3|NONE}
[:INPut]:SYNChronize:ELEMent<x>?
<x> = 1 to 7 (element)
EXTernal = External clock input (Ext Clk)
Z1 = Z Phase1 (ChD) (/MTR1 option required)
Z3 = Z Phase3 (ChH) (/MTR2 option required)
NONE = No synchronization source
:INPUT:SYNCHRONIZE:ELEMENT1 I1
Example
:INPUT:SYNCHRONIZE:ELEMENT1?
-> :INPUT:SYNCHRONIZE:ELEMENT1 I1
5-58
[:INPut]:SYNChronize:{SIGMA|SIGMB|SI
GMC}
Function
Collectively sets the synchronization source of all
the elements that belong to the specified wiring
unit (ΣA, ΣB, or ΣC).
Syntax
[:INPut]:SYNChronize:{SIGMA|SIGMB|
SIGMC} {U<x>|I<x>|EXTernal|Z1|Z3|
NONE}
<x> = 1 to 7 (element)
EXTernal = External clock input (Ext Clk)
Z1 = Z Phase1 (ChD) (/MTR1 option required)
Z3 = Z Phase3 (ChH) (/MTR2 option required)
NONE = No synchronization source
:INPUT:SYNCHRONIZE:SIGMA I1
Example
Description SIGMA, SIGMB, or SIGMC is invalid if the wiring
system setting ([:INPut]:WIRing) is made in such
a way that the corresponding wiring unit (ΣA, ΣB,
or ΣC) does not exist.
[:INPut]:SYNChronize:LEVel?
Function
Queries all synchronization source level settings.
[:INPut]:SYNChronize:LEVel?
Syntax
[:INPut]:SYNChronize:LEVel:{VOLTage|
CURRent}[:ALL]
Function
Sets the synchronization source level of the
{voltage|current} of all elements at once.
[:INPut]:SYNChronize:LEVel:{VOLTage|
Syntax
CURRent}[:ALL] {<NRf>}
<NRf> = -100.0 to 100.0(%)
Example
:INPUT:SYNCHRONIZE:LEVEL:VOLTAGE:
ALL 10
[:INPut]:SYNChronize:LEVel:{VOLTage|
CURRent}:ELEMent<x>
Function
Sets or queries the synchronization source level
of the {voltage|current} of the specified element.
[:INPut]:SYNChronize:LEVel:{VOLTage|
Syntax
CURRent}:ELEMent<x> {<NRf>}
[:INPut]:SYNChronize:LEVel:{VOLTage|
CURRent}:ELEMent<x>?
<x> = 1 to 7 (element)
<NRf> = -100.0 to 100.0(%)
:INPUT:SYNCHRONIZE:LEVEL:VOLTAGE:
Example
ELEMNT1 0
:INPUT:SYNCHRONIZE:LEVEL:VOLTAGE:
ELEMNE1?
-> :INPUT:SYNCHRONIZE:LEVEL:VOLTAGE:
ELEMNT1 0.0
IM WT5000-17EN