7.6 Replace pulse catch module

7.6 Replace pulse catch module
There are no available replacement modules for AnS (Small Type) Series pulse catch module A1SP60.
Replace it with one of the followings.
•‥L‥Series‥CPU‥:‥Built-in‥I/O‥pulse‥catch‥function
•‥Q‥Series‥CPU:‥Interrupt‥module‥QI60

7.6.1 Replace with LCPU built-in I/O pulse catch function

The address of the LCPU built-in I/O pulse catch function is determined by the I/O assignment
parameter and the built-in I/O function setting. Therefore, it is necessary to change the existing
address Xn to the address set for the LCPU built-in I/O pulse catch function.
● Replacement example
Example of existing configuration
A1S
A1SH
A1S
61PN
CPU
P60
The address depends on the module position
(16 points occupied).
(1) Example of LCPU parameter setting
The following parameters must be set to use the LCPU built-in I/O function.
Select "L parameter setting" -> "I/O assignment setting," and set the first XY to 0.
Select "L parameter setting" -> "Built-in I/O function setting," and specify the pulse catch function
for the input signal Xn0.
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com
I/O
I/O
I/O
module
module
module
Example of new configuration
L61P
Replace
The address (16 points occupied) and built-in
I/O function are set by the PC parameters.
154
I/O
I/O
I/O
L02CPU
module
module
module